    350KW Shangchai Diesel Generator

    Zhongjie Power 2024-11-14 15:06:21 93 Views

    350KW Shangchai Diesel Generator Real Shot (including Self Starting Control Cabinet), 18168300588 Phone and WeChat Same Number


    Generator set parameters

    Diesel engine parameter set model GF-350 model SC25G610D2

    Output power 300kw, suction mode, turbocharging

    Power factor COS Φ=0.8 (lagging) Cylinder count 12/V

    Output voltage 400V/230V cylinder diameter x stroke (mm) 135/150

    Output current 720A compression ratio 16:1

    Rated frequency 50Hz, calibrated power/speed kW/r/min, 350/1500

    Steady state voltage regulation rate (%) ≤± 2.5 1-hour power/speed kW/r/min 445/1500 voltage fluctuation rate (%) ≤± 0.3 Minimum fuel consumption rate g/(kW · h) ≤ 202

    Transient voltage regulation rate (%)+25~-30 Lubrication mode Pressure and splash mixed voltage stabilization time (s) ≤ 6 Starting mode Electric starting

    Steady state frequency adjustment rate (%) ≤± 5

    Fuel system electronic speed regulation frequency fluctuation rate (%) ≤± 1.5

    Transient frequency adjustment rate (%)+12~-10 Frequency stabilization time (S) ≤ 5

    Dimensions (mm) 3500 × 1570 × 2000 (mm)

    Unit weight (kg) 3650kg

    Noise (LP7m) dB (A) ≤ 95

    Generator: Zhongjie (available from brands such as Stanford, Marathon, Ingersoll, Leyland, Faraday, Audi, Lingyu, Evergrande, Landian, Magget, Deke, etc.)

    Model: ZJ-3500 Material: Pure Copper

    Frequency 50Hz, insulation level H

    Voltage control mode AVR protection level IP23

    Phase number/wiring three-phase four wire/Y-shaped winding frequency fluctuation rate (%) ≤± 0.5

    Voltage fluctuation rate (%) ≤± 0.5 Voltage regulation rate (%) ≤± 0.5 (steady state)+20~-15 (transient) Frequency regulation rate (%) ≤± 0.5 (steady state)+10~-7 (transient)